Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T06CM03169

Parcel: 124060100


Addresses:

837 E 8TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM03169

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/18/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
TAKE CARE OF ITEMS LISTED ON 9/12/06 FOR FINAL
NOTE: ISSUE TO GENERAL INSPECTOR
09/12/2006 ELECTRIC - INTERMEDIATE Denied 1. PROVIDE A SERVICE RECEPTACLE FOR ROOFTOP A.C EQUIPMENT -- NEC 210.63 (GFI PROTECTED -- NEC 210.8)
2. NEED TO USE A SEALING TYPE FITTING WHERE RACEWAY ENTERS PANEL ABOVE LIVE PARTS -- NEC 408.17
3. REPAIR SERVICE PANEL COVER SO IT CAN OPEN & CLOSE PROPERLY.

INTERIOR WAS LOCKED, I COULD NOT INSPECT INSIDE
WIRING @ THIS TIME.