Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM03169
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/18/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* TAKE CARE OF ITEMS LISTED ON 9/12/06 FOR FINAL NOTE: ISSUE TO GENERAL INSPECTOR |
|
09/12/2006 | ELECTRIC - INTERMEDIATE | Denied | 1. PROVIDE A SERVICE RECEPTACLE FOR ROOFTOP A.C EQUIPMENT -- NEC 210.63 (GFI PROTECTED -- NEC 210.8) 2. NEED TO USE A SEALING TYPE FITTING WHERE RACEWAY ENTERS PANEL ABOVE LIVE PARTS -- NEC 408.17 3. REPAIR SERVICE PANEL COVER SO IT CAN OPEN & CLOSE PROPERLY. INTERIOR WAS LOCKED, I COULD NOT INSPECT INSIDE WIRING @ THIS TIME. |