Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM03165
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/13/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
09/01/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. PROVIDE REJECTION PINS 2. CLEAN SURFACES UNDER LUG 250.12 |
|
06/23/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) BOND NEUTRALS TO SERVICE DISCONNECT ENCLOSURERS NEC 250.24 (B) 2) IDENTIFY SERVICE DISCONNECT NEC 230.70 (B) 3) NEED 2ND GROUND ROD FOR SERVICE NEC 250.53 4) INSTALL ADDRESS ON SERVICE 5) IDENTIFY PANEL DIRECTORY 6) ENERGIZE ROOF SERVICE OUTLET 7) ELIMINATE OLD GROUND RODS 8) NOTE: CALL FOR FINAL FOR MONDAY-OK FOR POWER |
|
06/22/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* AT SERVICE EQUIPMENT: 1. ROUTE NEUTRAL TO SERVICE DISCONNECT - NEC 250.24(B) 2. USE PROPER SIZE NEUTRAL - NEC 250.24 (B)(2) 3. BOND NEUTRAL TO DISCONNECT ENCLOSURE - NEC 250.24(B) 4. IDENTIFY SERVICE DISCONNECTS - NEC 230.70(B) 5. INSTALL GROUNDING ELECTRODE FOR SERVICE - NEC 250.50 6. INSTALL BONDING JUMPER - NEC 250.28 7. BOND ALL METAL ENCLOSURES AND RACEWAYS - NEC 250.92 WITH PROPER SIZE CONDUCTOR - NEC 250.102 (C) 8. ARRANGE BONDING CONDUCTORS TO PREVENT OBJECTIONABLE CURRENT - NEC 250.6 9. CT ENCLOSURE LID NEEDS TO OPEN TO 90 DEG. MINIMUM - NEC 110.32 ON ROOFTOP: 1. IDENTIFY PANEL DIRECTORY - NEC 408.4 2. NEED ROOFTOP SERVICE RECEPTACLE - NEC 210.63 3. NEED DISCONNECT THAT DISCONNECTS ALL UNGROUNDED CONDUCTORS FROM UNITS - NEC 440.11 4. IDENTIFY DISCONNECTS - NEC 110 (PARTIAL INSP. ONLY) |