Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/29/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 12/28/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE ANGLE IRON AROUND FIRE DAMPER IN CORRIDOR 2) SUPPORT FLEX DUCT ABOVE CORRIDOR 3) INSULATE SHEET METAL SUPPLY BOOTS 4) PERMANENTLY IDENTIFY UNITS AND DISCONNECTS 5) PROVIDE A SMOKE TEST ON DUCT SMOKE DETECTORS 6) PROVIDE AIR BALANCE REPORT |
|
| 12/21/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* FINISH AC UNITS ON ROOF PROVIDE A TEST ON DUCT SMOKE DETECTORS PROVIDE AIR BALANCE REPORT PROVIDE A LETTER FROM ENGINEER IF DELETING ANY FIRE DAMPERS. FINISH INSTALL ON ANY REMAINING DAMPERS. PROVIDE ACCESS DOORS. |