Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T06CM03163
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/28/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
09/29/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* DWV AND DOMESTIC WATER OK TO COVER AAV'S TO INSTALL ABOVE CEILING GAS TEST NOT ON PERMIT CARD, PLEASE ADD. GAS PIPING NOT YET INSTALLED. |
|
09/28/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - POST YOUR ADDRESS - DOUBLE FIXTURE FITTING REQUIRED AT DOUBLE FIXTURE CONNECTIONS . - HORIZONTAL CHANGE OF DIRECTION ON TRAP ARMS TO BE MADE WITH WYE PATTERN FITTING (SWEEP) - TR'S 37, 38, 39, 40, 36 AND DFS AT CORRIDOR 27 ARE OK TO COVER. - TR'S 41, 42, 43 AND 44 HAVE CORRECTIONS, RECALL FOR INSPECTION. - 1 1/2 VENT OK AT LAVS IN 43 & 44 |