Permit: T06CM03163

Parcel: 13803031T


Addresses:

850 W VALENCIA RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM03163

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/09/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/04/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. STILL NEED TO ADDRESS MAINT. RECEPTS ON ROOF
FROM ARCH PROVIDE DETAILS IF USING X-FORMERS TO SUPPLY RECEPTS UTILIZING AC UNIT POWER.
2. PANEL LW2 NEEDS COVER.
3. LABEL INSTA-HOTS IN RESTROOMS FOR DISCONNECT LOCATIONS.

OK FOR TCO TO OCCUPY
01/02/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
1. COMPLETE SUPPORTING PER NOTES, GFI RECEPTS ON ROOF NOT PER PLAN, J-BOXES STILL OPEN, ETC. SEE NOTES LAST INSP. A RE-INSPECTION FEE IS ASSESSED.

NEED LETTER FROM ARCH. TO ADDRESS REMOVAL OF PANEL LW3 EXIT LTS IN FRONT & BACK EXITS.
12/29/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LABEL INSTA-HOTS FOR DISCONNECTING MEANS IN CEILING
2) SUPPORT CONDUITS, MC AT #56 OFFICE-REPLACE MC CABLE (DAMAGED)
3) ADDRESS EXSISTING BREAKER PANEL AT SOUTH WEST CORNER OF BLDG TIE OFF BATH ENDS OF CEILING WIRES USED FOR SUPPORT. ROOM D-26 REPLACE DAMAGED MC CABLE SCREW DOWN FIXTURE IN GRID OR BEND OUT TABS SO THEY ARE EFFECTIVE. CLOSE UP J-BOXES, PANELS
4) NO GFCI'S ON ROOF, NO PANEL SCHEDULES
5) A REINSPECTION FEE WILL BE ASSESSED NEXT INSPECTION IF NO COMPLIANCE
12/28/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
12/21/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. COMPLETE SUPPORTS FOR MC & CONDUIT PER CODE
2. COMPLETE OWRK IN BACK OF BLD. AREA
3. UPDATE LABELS FOR EQUIP