Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM03158
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/19/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/18/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. AC DISCONNECTS TO HAVE PROPER FRONT WORKING CLEARANCE - 30" WIDE, 36" DEEP --- NEC 110.26 2. USE PROPER SIZED STRAPS FOR FLEX DISCONNECTS TO AC'S - NEC 110.3B 3. IDENTIFY AC 1 DATA PLATE 4. PANEL DIRECTORY NOT CORRECT - NEC 408.4 5. DISHWASHER/ELEVATOR NOT COMPLETE 6. GARAGE RECEPTACLE TO BE GFI PROTECTED |