Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM03141
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/07/2006 | FRAMING | Approved | IVRS - Inspection :* | |
11/02/2006 | FRAMING | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection Items 2, 4, 5, 10 and 13 from 10/31/06 inspection not done Refee |
|
10/31/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) STUCCO CUT WIRE AT BOXES 2) BOND GAS PIPE 3) 14-2 OUT OF CEILING GARAGE 4) 14-3 KITCHEN CEILING ? 5) COPPER OUT OF CEILING GARAGE 6) NO TEST ON SOLAR PLUMBING 7) NO SUPPLY OR DWV TEST 8) REPAIR AND REINSTALL BOOT IN DINING AND MASTER CLOSET 9) 2ND A/C DRAIN BLOCKS FURNACE PLATFORM 10) NAIL OFF HIP HANGERS IN GARAGE 11) TIGHTEN RED HEADS 12) BLOC A/C BOOT DINING AND MASTER CLOSET 13) ADD STUDS BESIDE STOVE DUCT HOOD 14) REPAIR RAT RUN OVER FURNACE |
|
10/30/2006 | FRAMING | Partial Approval | IVRS - Inspection :* 1) UNTIL ALL INTERMEDIATES ARE APPROVED |