Inspection Status: Approved

Inspection History: SHEET ROCK NAILING

Date Description Inspector Results Comments
08/30/2006 SHEET ROCK NAILING Approved IVRS - Inspection :*
08/29/2006 SHEET ROCK NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GARAGE CEILING UNDER OCCUPIED SPACE REQUIRES 5/8" TYPE X DRYWALL NAILED WITH 1 7/8" 6D NAILS SPACED AT 6" ON CENTER PER IRC TABLE 702.3.5 NOTE E. HAVE PLAN ? NOTE 17 CHANGED TO CODE AND APPROVED BY CITY
2) HOUSE OK-NOT GARAGE