Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM03121
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/07/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* HAVE ELECTRICAL CONTRACTOR GO THROUGH ENTIRE STORE ENSURE JOB IS 100% COMPLETE PER APPROVED PLANS AND MEETS NEC REQUIREMENTS |
|
04/04/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* MEAT DEPT INSPECTION ONLY 1. NEED REVISION TO DRAWING SHOWING ALL WORK 2. NEED TO INSTALL WEATHERPROOF RECEPT PER DRAWINGS 3. REMOVE ALL OLD ELECTRIC & DEBRIS FROM CEILING ABOVE MEAT DEPT. 4. SEAL ALL OPEN JUNCTION BOXES & MISSING KNOCKOUTS 5. CANNOT USE SJ CORD FOR PERMANENT WIRING OF BUILDING. SPOT COOLER. 6. NEED TO INSTALL DISCONNECT FOR ALL APPLIANCES PER NEC 422 7. NEED TO INSPECT CEILING ABOVE MEAT COUNTER. HAVE NO ACCESS TO JUNCTION BOXES AT LIGHT FIXTURES ALL DROP CEILING PANELS HAVE ITEMS IN THEM. 8. COMPLETE ALL ITEMS IN BAKERY AREA. |
|
01/18/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. DEMO BACK TO JUNCTION BOXES AND FILL UNUSED OPENINGS FITTINGS UNUSED DO NOT FILL - NO EXPOSED CONDUCTORS. 2. FINISH VDV STORE 3. FINISH LIGHTS BAKERS & GFCI'S 4. SUPPORT WIRES NEEDED FIXTURES - BACK OF STORE 5. WE HAVE EXPOSED CONDUCTORS IN COMBUSTIBLE MATERIAL - USE APPROVED BOXES AND CABLES OK DELI OK EM LIGHTING RECEIVED MONEY ORDERS: 55871576453 & 55871576454 |
|
01/17/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. FINISH PREVIOUS INSPECTION 1, 6 & 7 DELI * CHECK DELI & BAKERY NEXT TIME - GO THROUGH BAKERY BEFORE NEXT INSPECTION |
|
01/11/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* DELI 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE AT NON-COMBUSTIBLES OR FLUSH AT COMBUSTIBLES NEED AN APPROVED EXTENDER RING -- 314.20 2. KITCHEN RECEPTACLE TO BE AS PER 210.8 - GFCI OR SINGLE 3. GFI AT COUNTER NOT WORKING 4. FILL UNUSED OPENINGS IN BOXES 5. SUPPORT M/C CABLE AS PER CODES 6. VDV CABELING TO BE AS PER 725.3 & 6, 800.3 & 6 7. ATTACH FIXTURES TO GRID |
|
01/04/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. NEED PLAN REVISIONS A. UNDERGROUNDS B. PANEL SCHEDULES C. LIGHTING LOAD CALCULATIONS AND FIXTURE SCHEDULES 2. INSPECTIONS WILL BE PERFORMED IN AREAS ACCESS TO CEILINGS AND DEVICES WILL NEED TO BE ACCOMODATED. OK STARBUCK FINAL SUBJECT TO REVISIONS. |
|
12/21/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO ONE ON SITE NO PLANS NO MESSAGE NO DIRECTIONS TO MANAGER - PLEASE HAVE CONTRACTOR RECALL FOR INSPECTION AND HAVE PLANS HERE IN ORDER TO GO OVER FINAL. |
|
08/15/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. NOTE ALL REVISIONS NEED TO GO THROUGH ORIGINAL PLAN REVIEWER (STANTEC) HAVE THE STAMPED APPROVED REVISION ON JOB SITE APPROVED BY CITY OF TUCSON - STANTEC. 2. INSTALL PROTECTIVE BUSHING ON 1 1/4" FLEX CONNECTOR IN PANEL FEEDING PANEL. 3. REVISE PANEL SCHEDULE SE & LOADS TO REFLECT ADDED EQUIP. & RELOCATED CIRCUITS. |