Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T06CM03121
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/02/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK SOUTH 2) OK CENTER STAND 3) OK NORTH PRODUCE STAND 4) 3-3/4" CONDUIT EACH |
|
11/01/2006 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* | |
10/23/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
10/09/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* WALLS DRINKING FOUNTAIN PANINI SANDWICH CASE |
|
09/27/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* DELI, CHEESE, FOUNTAIN, OLIVE, PASTRY, NOTE: SECURE E.M.T BEHIND FOUNTAIN PER N.E.C 3' FROM J-BOX. |
|
09/20/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. 30' 1" PVC -- APPROX. 25' WALL TO NEW LOCATION 2. 2- 3/4" PVC'S DELI AREA OK TO COVER |
|
07/31/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. PLEASE REVISE PLANS FOR CONDUITS. INSTALLED DIFFERENT THAN PLANS. OK PVC CONDUITS WALL TO STARBUCKS SUBJECT TO APPROVAL OF REVISION. |
|
07/28/2006 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* ANSWER YOUR PHONE!!! IF NOT LEAVE ME DETAILED INSTRUCTIONS ON WHAT YOU WANT INSPECTED & KNOW IT WILL NOT BE MY JOB TO UNCOVER TEMP. FLOOR OVER TRENCHES. |