Permit: T06CM03118

Parcel: 11704301A


Addresses:

536 N 4TH AV #01

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
04/23/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
FLANGES OK
04/21/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CLOSET FLANGES TO EXTEND 1/4" ABOVE FINISHED FLOOR
03/12/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK TO COVER ALL AREAS
2. NEED TO SEE FLANGES AFTER FINISHED FLOOR IS SET
03/11/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. SEE NOTE #4 FROM 03/04/08
2. NEED TO SEE HOT INSULATED
3. NEED TO REINSPECT FLANGES PRIOR TO SETTING WATER CLOSETS
03/04/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. I HAVE NO NOTES ON ANY OF THE DEMO'D PIPING HAVING BEEN INSPECTED
2. HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION
TO BE A SWEEP
3. WOOD SHIMS ARE NOT APPROVED SUPPORT FOR PIPING
4. OK TO INSULATE HOT 3" CLEANOUTS REQUIRE 18" IN FRONT
5. ABS IS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OF ELEVATION AND AT THE END OF BRANCHES, THEN NO MORE THAN FOUR FEET BETWEEN HANGERS
6. CLOSET FLANGES TO EXTEND 1/4" ABOVE FINISHED FLOOR
FLOOR DRAIN TO BE FLUSH WITH FINISHED FLOOR