Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/23/2008 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* FLANGES OK |
|
| 04/21/2008 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CLOSET FLANGES TO EXTEND 1/4" ABOVE FINISHED FLOOR |
|
| 03/12/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK TO COVER ALL AREAS 2. NEED TO SEE FLANGES AFTER FINISHED FLOOR IS SET |
|
| 03/11/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SEE NOTE #4 FROM 03/04/08 2. NEED TO SEE HOT INSULATED 3. NEED TO REINSPECT FLANGES PRIOR TO SETTING WATER CLOSETS |
|
| 03/04/2008 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. I HAVE NO NOTES ON ANY OF THE DEMO'D PIPING HAVING BEEN INSPECTED 2. HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP 3. WOOD SHIMS ARE NOT APPROVED SUPPORT FOR PIPING 4. OK TO INSULATE HOT 3" CLEANOUTS REQUIRE 18" IN FRONT 5. ABS IS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OF ELEVATION AND AT THE END OF BRANCHES, THEN NO MORE THAN FOUR FEET BETWEEN HANGERS 6. CLOSET FLANGES TO EXTEND 1/4" ABOVE FINISHED FLOOR FLOOR DRAIN TO BE FLUSH WITH FINISHED FLOOR |