Permit: T06CM03112

Parcel: 12704037B


Addresses:

5000 E SPEEDWAY BL

Inspection Status: Partial Approval

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
07/06/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
07/06/2006 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
06/22/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
UNDERGROUND WASTE PIPING - OFFSET CLOSET IS OK
OK TO COVER BELOW GROUND PIPING ONLY.
OTHER ITEMS FROM PREVIOUS INSPECTION STILL REQUIRED
CLOSET FLANGE INSPECTION REQUIRED.
06/16/2006 PLUMBING - ROUGH, SOIL Denied 1818 DOOR CODE
702-596-1555
1. WYE PATTERN DRAINAGE FITTING REQUIRED FOR HORIZONTAL TO HORIZONTAL CHANGE OF DIRECTION.
2. I'M NOT HAPPY WITH WHITEOUT REVISIONS ON PLAN. PROVIDE CITY APPROVED PLAN WITHOUT WHITED OUT PLUMBING NOTES.
3. WC MOVED TWO FEET, WATER SUPPLY TO WC ALSO NEEDS TO MOVE.
4. CLOSET STUB SHALL BE EVEN W/TOP SURFACE OF FLANGE.
5. CONDENSATE CANNOT TIE INTO WC VENT.
PIPE CONDENSATE TO APPROVED LOCATION.
THIS IS A HEALTH AND SAFETY ISSUE
RECALL 03005 AND 03035