Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/17/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/13/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
ROOF:
1. PROTECT SEAL TITE FROM SHARP METAL EDGES.
2. SEPARATE GROUNDS AND NEUTRALS AT A/C DISCONNECTS ALSO REMOVE BOND SCREW IF LEFT AS A NEUTRAL BAR.

SPACE:
1. CLEAN EXCESS PAINT OFF OF DEVICE TERMINALS 110.12
2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20
3. BATH GFI NOT WORKING.
4. LIGHTING NOT AS PLAN -- PLEASE REVISE PLANS AND ENERGY CALC'S.
5. KITCHEN RECEPTACLES TO BE GFCI AS PLANS AND 210.8
6. FILL USUSED OPENING IN PANEL.