Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/13/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/06/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*. 1) FINISH #5 PREVIOUS ITEM 2) SUPPORT VDV CABELING |
|
| 09/25/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. IF SCREWS 4 ON CORNERS 2. MAKE UP AND GROUND BOXES 3. SUPPORT CONDUIT WITHIN 3' OF BOXES 4. GROUND JUNCTION BOXES 5. NEED REJECTION PINS 6. USE APPROVED FITTING WITH LB NOT CHASE NIPPLE. 7. BOND SERVICE NIPPLE. |
|
| 09/12/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | OK EXTERIOR WALL OK PVC CONDUIT UNDER SLAB |
|
| 08/22/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK BATHROOM WALLS & HARD LID OK EXTERIOR WALLS EXCEPT AT PANELS 1. SUPPORT CONDUIT WITHIN 3' OF PANEL |
|
| 08/21/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* DISCUSSED SERVICE LOCATION |