Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/03/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* REVISED PLAN DATED 8/9/06 ON SITE SHOWS ISOMETRIC VIEW OF P-4 CLOSET FLANGES OK |
|
| 11/02/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE NOTE FROM 9/20/06 AND SECURE PROPERLY SEE NOTES FROM 7/26/06 & 7/19/06 AND PROVIDE PLAN AS REQUESTED. |
|
| 09/20/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* - CLOSET FLANGES SHALL SET ON A FIRM BASE WITH TOP OF FLANGE 1/4" ABOVE THE SURFACE THAT THE TOILET SETS ON. - YOUR FLANGE IS BELOW F.F THIS NEEDS TO BE CORRECTED. |
|
| 08/11/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. YOU STILL HAVE NOT FRAMED IN AN ACCESS DOOR FOR CW SOV 2. YOU STILL HAVE NOT SECURED CLOSET FLANGE/RING TO FLOOR W/SCREWS AS REQUIRED BY THE UPC ON PAGE 320 SECTION 314.2 |
|
| 07/26/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - PIPE WRAPS OK - YOUR PLANS ON SITE DO NOT REFLECT THE INSTALLATION - YOU ARE MISSING P-4 - YOU HAVE PIPED COLD WATER ONLY TO LAVS - ALL PIPING IN WALLS MEET CODE REQUIREMENTS. - OK TO COVER WALLS PROVIDED THAT YOU PROVIDE A PLAN REVISION BEFORE FINAL INSPECTION. - PROVIDE ACCESS FOR CW SOV ABOVE MENS LAV - CLOSET FLANGES ARE NOT INSTALLED IN ACCORDANCE W/UPC ABS INSTALLATION STANDARDS (15.5) - CORRECT FLANGE INSTALLATION AND CALL FOR INSPECTION BEFORE SETTING WCS |
|
| 07/19/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* THERE ARE 2 APPROVED PLANS FOR THIS SPACE AND NEITHER IS THIS INSTALLATION. PROVIDE REVISED APPROVED PLAN OF YOUR INSTALLATION |
|
| 07/18/2006 | PLUMBING - INTERMEDIATE | Cancelled | IVRS - RI canceled |