Permit: T06CM03109

Parcel: 13322471B

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
08/11/2006 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
REVISED PLANS ARE OK. YOU SHOULD ALSO HAVE CALLED FOR 3005 INSPECTION I WILL ENTER THIS FOR YOU
07/26/2006 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
07/03/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
WATER TEST WASTE & VENT THRU ROOF OK
1. PROVIDE PIPE WRAPS PRIOR TO CONCRETE POUR WILL SEE AT INTERMEDIATE.
2. REDLINE ON SITE. SHALL HAVE REDLINE & REVISED APPROVED PLAN ON SITE. PROVIDE MEANS FOR TEMPERING WATER SUPPLY TO LAVS ON THIS REVISION. WITH DELETION OF P-3 AND REDLINES.
06/29/2006 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
CALLED AND LEFT MESSAGE AT ABOUT 9 AM
9:50 DOOR LOCKED.
06/28/2006 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLAN HAS WRONG ADDRESS
2) NOINSTALLED PER PLAN
3) MISSING P-3
4) ALSO PROVIDE 1/4" PER FOOT SLOPE ON AL PIPING
5) PIPING SHALL BE PROPERLY ? WITHOUT STRAIN (VENT AT P-2)