Permit: T06CM03108

Parcel: 115040950


Addresses:

1321 N EUCLID AV


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T06CM03108

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
10/17/2006 FRAMING Approved IVRS - Inspection :*
09/12/2006 FRAMING Partial Approval IVRS - Inspection :*
1) PEDNING MECHANICAL INTERMEDIATE
2) WORK NOT COMPLETE
09/11/2006 FRAMING Partial Approval PENDING ALL TRADES
08/28/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE AIR GAGE AT 10 POUNDS
2) SHADE WATER TEST DWV SYSTEM
3) PROVIDE WATER TEST DWV SYSTEM
4) TRACER WIRE MAIN SEWER
5) NAIL PROTECT PLUMBING THRU-OUT UNDER 1 1/2"
6) TPR LINE MUST BE HARD PIPED
7) PROVIDE 1" CLEARANCE COMBUSTIBLE MATERIALS WATER HEATER FLUE B-VENT
8) TERMINATE EXHAUST TO EXTERIOR
9) EXPOSE COPPER BOND
10) PROVIDE GAS BOND
11) PROVIDE HIGH/LOW COMBUSTION RELIEF TO EXTERIOR