Permit: T06CM03099

Parcel: 13319195A


Addresses:

6700 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
08/17/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
08/07/2006 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
CALL MARCO 907-3773

15 PSI PRESSURE TEST IS OK
PIPING PER PLAN OK
WRAP ALL TOOL MARKS, THEN YOU CAN COVER
08/03/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
PIPE SIZE NOT PER PLAN
USE A PRESSURE GAUGE WITH 1/10 PSI INCREMENTATIONS.
INSTALL PIPING PLUMB, LEVEL AND SQUARE WITH NO BENDS OR STRAIN ON PIPING. SUPPORT PIPING AT 8' MAX
WRAP ALL TOOL MARKS ON BELOW GRADE PIPING
A SEDIMENT TRAP IS REQUIRED AT EQUIPMENT
PROVIDE VENT CAP.