Permit: T06CM03086

Parcel: 13106034A

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T06CM03086

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/22/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
02/02/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
09/13/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
- ICEE PIPING W/TEST OK
- HAND SINK PIPING NOT PROPERLY SUPPORTED
- SUPPORT HORIZONTAL ABS AND SECURE BRACKET ON VERTICAL PIPING.
- CLEAN OUT SHALL BE ACCESSIBLE
- CAP OPEN SEWER PIPE ASAP
- NEVER LEAVE OPEN DWV PIPING, ESPECIALLY IN AN OPEN BUSINESS.
- SERIOUS HEALTH VIOLATIONS CAN RESULT IN FEES AND STORE CLOSURE.
09/12/2006 PLUMBING - INTERMEDIATE Partial Approval BEFORE HOURS INSPECTION PAID W/CHECK #021861

1. HAND SINK MOVE 3' OK -- RED LINE PLAN ADD PIPE SUPPORT.
2. 13 BACKFLOW DEVICES INSTALLED. PROVIDE CERTS INDIRECT DRAINS AT SODA FOUNTAINS OK.
3. ADD PIPE SUPPORT. CORRECT DRAINS FOR ICEE MACHINES. RETEST. REINSPECT.
4. EXISTING WATER HEATER DOES NOT HAVE EXPANSION CONTROL, THIS IS A POTENTIAL SAFETY HAZARD. AS THIS IS A CLOSED SYSTEM.
PLEASE PROVIDE AN EXPANSION TANK.