Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T06CM03086
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/22/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 02/02/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 09/13/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - ICEE PIPING W/TEST OK - HAND SINK PIPING NOT PROPERLY SUPPORTED - SUPPORT HORIZONTAL ABS AND SECURE BRACKET ON VERTICAL PIPING. - CLEAN OUT SHALL BE ACCESSIBLE - CAP OPEN SEWER PIPE ASAP - NEVER LEAVE OPEN DWV PIPING, ESPECIALLY IN AN OPEN BUSINESS. - SERIOUS HEALTH VIOLATIONS CAN RESULT IN FEES AND STORE CLOSURE. |
|
| 09/12/2006 | PLUMBING - INTERMEDIATE | Partial Approval | BEFORE HOURS INSPECTION PAID W/CHECK #021861 1. HAND SINK MOVE 3' OK -- RED LINE PLAN ADD PIPE SUPPORT. 2. 13 BACKFLOW DEVICES INSTALLED. PROVIDE CERTS INDIRECT DRAINS AT SODA FOUNTAINS OK. 3. ADD PIPE SUPPORT. CORRECT DRAINS FOR ICEE MACHINES. RETEST. REINSPECT. 4. EXISTING WATER HEATER DOES NOT HAVE EXPANSION CONTROL, THIS IS A POTENTIAL SAFETY HAZARD. AS THIS IS A CLOSED SYSTEM. PLEASE PROVIDE AN EXPANSION TANK. |