Permit: T06CM03073


Addresses:

4175 N FORTUNE LP

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
01/05/2007 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
OK FOR SHEETROCK
12/19/2006 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE KITCHEN EXHAUST AS PER PLANS
IF YOUR MECHANICAL CONTRACTOR CONTINUES TO FAIL INSPECTION FOR THE SAME ITEMS OVER & OVER, A REFEE WILL BE CHARGED EACH TIME.
12/06/2006 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE KITCHEN EXHAUST DUCTING
2. DO NOT USE INSERT FITTINGS ON CONDENSATE DRAIN AS NOTED ON PREVIOUS INSPECTION.
11/14/2006 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
- EXTEND DRYER VENT OUT OF WALL OR PROVIDE A DRYER VENT BOX.
- INSERT FITTINGS USED FOR CONDENSATE DRAIN PIPING ARE NOT 3/4" I.D & RESTRICT THE FLOW OF DRAIN WATER.
- ALL DRAIN PIPE & FITTINGS MUST MEASURE 3/4" INTERNAL DIAMETER.