Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/13/2006 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 10/10/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* - PROVIDE CONDENSATE DRAINS AS NOTED ON PREVIOUS INSPECTION. - INSULATE SHEET METAL FITTINGS AT ROOF PENETRATIONS - HOW WILL THE SYSTEM BE AIR BALANCED WITHOUT VOLUME DAMPERS INSTALLED? |
|
| 09/26/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* PROVIDE CONDENSATE TO AN APPROVED LOCATION. STRAP ALL FLEX EVERY 5' & UP OFF OF GRID & TILES. INSTALL T-STAT WIRE. |
|
| 08/15/2006 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* DUCT SYSTEM NOT INSTALLED PER PLAN. |