Permit: T06CM03068

Parcel: 13322471B

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
12/13/2006 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
10/10/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
- PROVIDE CONDENSATE DRAINS AS NOTED ON PREVIOUS INSPECTION.
- INSULATE SHEET METAL FITTINGS AT ROOF PENETRATIONS
- HOW WILL THE SYSTEM BE AIR BALANCED WITHOUT VOLUME DAMPERS INSTALLED?
09/26/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
PROVIDE CONDENSATE TO AN APPROVED LOCATION.
STRAP ALL FLEX EVERY 5' & UP OFF OF GRID & TILES.
INSTALL T-STAT WIRE.
08/15/2006 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
DUCT SYSTEM NOT INSTALLED PER PLAN.