Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/13/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/06/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS NEW CUBICLE. |
|
| 09/25/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* FINISH PREVIOUS ITEMS #1 & #2 (12" FROM RING) |
|
| 09/20/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. PROTECT M/C CABLE AT TOP PLATE 2. SUPPORT VDV CABELING IN WALLS 725.6 & 800.6 & CEILING 3. PROTECT VDV CABELING IN WALLS FROM SHARP METAL EDGES. 4. GROUND ALL METAL BOX 5. SUPPORT AND SECURE M/C CABLE AT 6' INTERVALS ON THE HORIZONTAL. 6. CONDUIT NOT TO BE SUPPORTED OFF OF CONDUIT. |