Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/12/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/21/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE ADD 02036 TO PERMIT 2. SUPPORT VDV CABLEING AS PER 725.6 & 800.6 3. M/C CABLE TO BE INDEPENDENTLY SUPPORTED 300.11 |
|
| 08/17/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) NOTE: SUPPORT FEEDER RACE WAYS NO MORE THAN 10' TIGHTEN ALL SET SCREWS 2) TIGHTEN BOND (FIRE SPRINKLER) SET SCREWS |
|
| 07/14/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK HARD LIDS |
|
| 07/12/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER ELECTRICAL IN WALLS *NOTE: I DO NOT SEE ANY PROVISIONS FOR EMERGENCY/EXIT LIGHTING ON PLANS? |
|
| 07/11/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |