Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T06CM03052
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/30/2007 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* FINISH SEALING & INSULATING DUCTING OK FOR CEILING TILES NEED TO TEST FINAL WATER PIPE CONNECTIONS. |
|
02/05/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) CHECKED DRYER VENT IN WALL OK TO COVER 2) OK TO SHEETROCK HARD LIDS-WILL CHECK DUCTING THRU ACCESS OPENING 3) R5 DUCT WRAP REQUIRED IN UNCONDITIONED SPACER. 1 1/2" WRAP IS R4.2 |
|
11/20/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | 100 PSI TEST ON CHILLER PIPE OK TO INSULATE |