Permit: T06CM03052

Parcel: 12701001B


Addresses:

421 N ARCADIA AV

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
03/30/2007 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
FINISH SEALING & INSULATING DUCTING
OK FOR CEILING TILES
NEED TO TEST FINAL WATER PIPE CONNECTIONS.
02/05/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) CHECKED DRYER VENT IN WALL OK TO COVER
2) OK TO SHEETROCK HARD LIDS-WILL CHECK DUCTING THRU ACCESS OPENING
3) R5 DUCT WRAP REQUIRED IN UNCONDITIONED SPACER. 1 1/2" WRAP IS R4.2
11/20/2006 MECHANICAL - ABOVE CEILING Partial Approval 100 PSI TEST ON CHILLER PIPE OK TO INSULATE