Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T06CM03052
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/18/2007 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
04/13/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 100 PSI TEST ON CHILLER PIPE IN EQUIPMENT ROOM OK TO INSULATE |
|
03/22/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK FOR CEILING TILES 2ND FLOOR |
|
02/27/2007 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
02/22/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CHECKED FIRE DAMPERS SOUTH STAIRWELL OK TO SHEETROCK LID |
|
02/21/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* FIRE CAULK GAPS IN CORNERS & WHERE ANGLE IS NOT FLUSH TO WALL. FILL IN ABOVE SUPPLY DAMPER. ANGLE IRON IS NOT INSTALLED CORRECTLY OTHER SIDE OF WALL. |
|
02/14/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PROVIDE ANGLE IRON AROUND FIRE/SMOKE DAMPERS. FILL IN THE GAP ABOVE SUPPLY DUCT. EQUIPMENT ROOM DAMPERS FIL GAP ABOVE FIRE DAMPERS. RECEIVED MEMO ALLOWING DUCT INSULATION. |
|
02/01/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CHECKED 100 PSI TEST ON 1ST FLOOR HYDRONIC PIPING 2) OK TO INSULATE |
|
01/30/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PROVIDE MIN. 100 PSI HYDROSTATIC TEST ON ALL HYDRONIC PIPING. INSTALLATION IS OK OK FOR PARTIAL INSULATION |
|
11/21/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* INSULATION ON CHILLER PIPE OK TO COVER |
|
11/17/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
11/16/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PROVIDE TEST ON CHILLER PIPING AS PER SECTION 1208.1 2003 IMC PROVIDE SPECS FOR INSULATION |