Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/18/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL CONTRACTOR TO FIRE SEAL RACEWAY SLEEVES AT BOTH ENDS |
|
| 05/15/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* PRODUCT PAPERWORK DOES NOT VERIFY LISTING 110.3(B) NEED TO CONTACT MANUFACTURE TO IDENTIFY LISTING MARKING. |
|
| 05/11/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PLEASE VERIFY LISTING AND LABELING FOR ORANGE PVC DUCT 2) FINISH BOX EXTENTIONS 314.20 |
|
| 05/10/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE IN NON-COMBUSTIBLE NEED APPROVED EXTENDER 314.20 2. VDV CABELING TO BE SECURE UPON EXITING CABLE TRAY 3. CANNOT USE SHEETMETAL SCREWS FOR GROUNDING 250.8 ALSO, CLEAN SURFACE UNDER LUG |