Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM03052
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/18/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
04/12/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. LABEL MAIN DISCONNECT AND PANELS ON OUTSIDE OF COVERS 2. FINISH VDV CABLING OK TO TILE EXCEPT AT CABLE TRAYS OK TO ENERGIZE POWER UNDER SUPEVISION OF ELECTRICIAN |
|
04/02/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* FINISH PREVIOUS ITEMS |
|
03/30/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE NOTES #2 LAST INSP. |
|
03/22/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. ATTACH FIXTURES TO GRID 410.16 - IF MANUFACTURES CLIPS ARE USED THEY MUST BE EFFECTIVE. 2. NOTE: GROUND JUNCTION BOXES 3. SUPPORT WIRES TO BE AS PER 300.11 4. USE APPROVED METHODS TO SECURE CABLES EXITING CABLE TRAY NOT TAPE. 5. NEED TO SEE INSTRUCTIONS FOR SENSORS |
|
01/29/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SUPPORT CONDUIT PER CODE 2. IF EM BALLAST WILL NOT STAY IN PLACE CONSULT MANUFACTURES FOR PROPER HOLD METHOD. 3. PULL CONDUCTORS TO CANS AND MAKE-UP |