Permit: T06CM03034

Parcel: 140180360


Addresses:

5003 S PARK AV #01

Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Date Description Inspector Results Comments
10/10/2006 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection :*
10/09/2006 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE APPROVED PLANS AND INSPECTION RECORD CARD.
10/03/2006 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
CMU CENTER WALL DETAIL 3 ON SHEET 2
VER. #4 @ 48" O.C @ 16" O.C TIES
SECOND LIFT AT BOND BEAM WITH #4 CONT. 11'-5" A.F.F.E
10/02/2006 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE ACCESSIBILITY FOR REINFORCED MASONRY PRE-GROUT INSPECTION. NOT APPROVED FOR GROUT WITHOUT INSP.
09/29/2006 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
PARTIAL APPROVED CENTER WALL DETAIL #3 ON SHEET 2
FIRST LIFT 4'0" WITH #4 @ 48" O.C & TIES @ 16" O.C