Permit: T06CM03032

Parcel: 12510003G


Addresses:

3485 E BROADWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Date Description Inspector Results Comments
08/23/2007 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
08/22/2007 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*
PROVIDE APPROVED SITE PLANS ON SITE FOR YARDWATER
07/19/2007 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
CONSTRUCTION WATER SHALL BE PROTECTED FROM BACKFLOW - REMOVE WATER HOSES OR I WILL HAVE YOUR METER LOCKED OFF.
02/28/2007 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
24 HR PSI AT 65 PSI ON YARD WATER
FROM BUILDING SERVICE TO RP LOCATION OK
STILL HAVE NOT SEEN AN APPROVED PLAN
02/27/2007 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
65 PSI ON GAUGE
LEAVE PSI ON WITHOUT INTRODUCING ANY MORE AIR
RECALL FOR INSPECTION, PROVIDE SITE PLAN
02/14/2007 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
2" TYPE K SERVICE W/BRAZED JOINT AT WATER SERVICE.
02/06/2007 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*