Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM03032
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/10/2007 | ELECTRIC - FINAL | Approved | ||
10/08/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION ONLY 1. EMERGENCY LIGHTING TO ALL BE WORKING/PER PLAN CUT IN TEST SWITCHES FOR EXTERIOR E-CANS 2. CASH WRAP AREAS SHOW INCORRECT POLARITY ON RECEPTACLES 3. BOND OR 250V FOR CONCENTRICS AS NEEDED 4. PLUG CHECK, CHECK PANEL DIRECTORIES 5. CHECK FOR PLAN CALLED FOR INCREASED CONDUCTOR SIZES |
|
10/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR ROOFTOP 1. ALL ROOFTOP UNITS TO HAVE DATA PLATES PROPERLY IDENTIFIED AND OVERCURRECT PROTECTION PER DATA PLATE 2. IN SIGN ATTIC - USE MC STRAPS FOR MC, NOT TAPE, MC TO BE SECURED WITHIN 12" OF TERMINATIONS. INSPECTION FOR SERVICE ROOM 1. TRANSFORMER "SWL" TO CONNECT TO BUILDING STEEL AND BOND NEUTRAL TO ENCLOSURE 2. NEUTRALS FOR DIFFERENT SYSTEMS TO HAVE SEPARATE IDENTIFICATIONS WHEN IN SAME ENCLOSURE -- 200.6 |
|
08/30/2007 | ELECTRIC - FINAL | Partial Approval | OK FOR TCO FOR STOCKING | |
08/29/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* WORK IN PROGRESS, CALL WHEN 100% COMPLETE |