Inspection History: ELECTRIC - FINAL

Permit Number - T06CM03032

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/10/2007 ELECTRIC - FINAL Approved
10/08/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION ONLY

1. EMERGENCY LIGHTING TO ALL BE WORKING/PER PLAN
CUT IN TEST SWITCHES FOR EXTERIOR E-CANS
2. CASH WRAP AREAS SHOW INCORRECT POLARITY ON RECEPTACLES
3. BOND OR 250V FOR CONCENTRICS AS NEEDED
4. PLUG CHECK, CHECK PANEL DIRECTORIES
5. CHECK FOR PLAN CALLED FOR INCREASED CONDUCTOR SIZES
10/05/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR ROOFTOP
1. ALL ROOFTOP UNITS TO HAVE DATA PLATES PROPERLY IDENTIFIED AND OVERCURRECT PROTECTION PER DATA PLATE
2. IN SIGN ATTIC - USE MC STRAPS FOR MC, NOT TAPE, MC TO BE SECURED WITHIN 12" OF TERMINATIONS.

INSPECTION FOR SERVICE ROOM
1. TRANSFORMER "SWL" TO CONNECT TO BUILDING STEEL AND BOND NEUTRAL TO ENCLOSURE
2. NEUTRALS FOR DIFFERENT SYSTEMS TO HAVE SEPARATE IDENTIFICATIONS WHEN IN SAME ENCLOSURE -- 200.6
08/30/2007 ELECTRIC - FINAL Partial Approval OK FOR TCO FOR STOCKING
08/29/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
WORK IN PROGRESS, CALL WHEN 100% COMPLETE