Permit: T06CM03032

Parcel: 12510003G


Addresses:

3485 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - CONSTRUCTION POWER

Permit Number - T06CM03032

Inspection Description - ELECTRIC - CONSTRUCTION POWER

Inspection Status - Approved

Date Description Inspector Results Comments
08/06/2007 ELECTRIC - CONSTRUCTION POWER Approved IVRS - Inspection :*
07/06/2007 ELECTRIC - CONSTRUCTION POWER Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION ONLY
1. NEED TO POST BOND FOR TEMP POWER
2. PROVIDE TORQUE LETTER
3. HAVE UNDERSIZE BONDING CONDUCTORS FOR SECONDARY RACEWAYS -- NEC 250.66
4. PROVIDE PERFORMANCE TEST -- NEC 230.95C
5. INSTALL MAIN BONDING JUMPER -- NEC 110.3B, 250
6. PLANS CALL FOR 50K AIC MAIN BREAKER BUT THIS ONE APPEARS TO BE 35K @ 30-480 CONTRACTOR TO PROVIDE VERIFICATION VIA LETTER FROM THE ELECTRICAL ENGINEER OF RECORD FOR PROPER OVERCURRENT DEVICES THROUGHOUT -- PLANS ARE VAGUE -- NEC 110.9
7. PROVIDE ILLUMINATION FOR SERVICE -- NEC 110.26D
8. PULL HOUSE FEEDER & MAKE UP -- IDENTIFY DISCONNECTS
NEC 110

WILL LOOK AT ROSS EQUIPMENT ROOM NEXT TIME
02/06/2007 ELECTRIC - CONSTRUCTION POWER Not ready for Inspection IVRS - Inspection :*