Permit: T06CM03032

Parcel: 12510003G


Addresses:

3485 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Date Description Inspector Results Comments
08/06/2007 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection :*
NOTE:
1. NEED PANIC HARDWARE FOR SERVICE ROOM DOOR
NEC 110.26
2. MAIN BONDING JUMPER FOR SERVICE TO BE CHANGED TO 500KMIL CU ASAP
3. DO NOT ENERGIZE FEEDERS BEFORE SAFE TO DO SO
07/06/2007 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection :
See detailed listing on site.| 999*