Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM03032
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/10/2007 | ELECTRIC - ABOVE CEILING | Approved | ||
08/21/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK MAIN SALES FLOOR |
|
08/17/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* ELECTRICAL SUPPORT WIRES TO BE AS PER 300.11 OK TO TILE SALES FLOOR EXCEPT AS NOTED |
|
08/16/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. CAP UNUSED CONDUITS 110.12 2. SUPPORTS FOR ELECTRICAL TO BE AS PER 300.11 3. M/C CABLE OVER 6' TO BE SUPPORTED 330.30 |
|
05/24/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. SCREW NOT ALLOWED IN FRONT PORTION OF BOXES 314.23 OK WALLS ROOM #104, 105, 118, 107 NORTH WALL #115 NO FURTHER INSPECTION UNTIL CORRECT INSPECTION NUMBER ADDED TO PERMIT 02035 |
|
05/16/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK WEST WALL #104 OK NORTH WALL #109 CALL IN BIGGER AREAS TO AVOID ADDITIONAL FEES |
|
05/10/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO COVER THE INTERIOR WALLS ONLY OF ROOM #112 |