Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM03030
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/31/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* CONTRACTOR HAS REVISED PLAN TO DELETE 220 TO DRYER/RANGE TO GAS APPLIANCES |
|
02/15/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PIG TAIL NEUTRALS ON 3 WIRE HOMERUNS 2. PLANS SHOW A 220V DRYER AND RANGE RECEPTACLE BUT THEY ARE NOT IN? OK COVER |
|
01/02/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER COMMON WALLS |
|
12/28/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* INSPECTION FOR COMMON WALL ONLY: 1) NAILS NOT ALLOWED IN BOXES-NEC 314.23 B1 2) DISPOSAL SWITCH BOX OVER FILLED-NEC 314.16 3) FINISH WIRING TO COUNTER RECEPTACLES 4) NAIL PLATE AS NEEDED-NEC 300.4 |