Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/19/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/11/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. MISSING EMERGENCY LIGHT 2. 120V KITCHEN RECEPTACLES TO BE GFI PROTECTED - NEC 210.8B 3. MISSING BATH LIGHTS, CHECK SENSOR 4. SEAL RACEWAYS INTO WALK IN, SELF TAP SCREWS NOT ALLOWED FOR GROUND -- NEC 300, 250.8 5. CHECK WIRING TO WALK IN, I CAN'T FIND DATA PLATE, DISC. 6. ON ROOF -- PROPER FUSE SIZE, FINISH M.U.A WIRING REPAIR ACCESS DOOR FOR BLOWER. 7. GROUND CEILING J-BOXES, CONTACTORS AND REMOVE WOOD FROM ENCLOSURE. |