Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T06CM03018
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/10/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* OK FOR FINAL |
|
04/04/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE INSTALL INSTRUCTIONS FOR FAN COILS BUILD TRAPS PER MANUFACTURES INSTRUCTIONS YOU CANNOT RUN UPHILL AFTER TRAP EVERYTHING ELSE IS OK |
|
03/26/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PERMANENTLY ID FAN COILS AND CONDENSORS 2) CONDENSATE DRAINS NOT SLOPED TRAPS TOO DEEP 3) LINE SET BLOCKING REMOVAL OF BLOWER ASSEMBLY 4) BUILD TRAPS PER MANUFACTURERS INSTRUCTIONS 5) FACTORY TRAPS ARE FLATTENED AT BOTTOM OF TRAP 6) PROVIDE SUPPORT UNDER 2 LONG LINE SETS AT CONDENSORS |