Permit: T06CM03018

Parcel: 11703295E


Addresses:

708 N ARIZONA AV


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T06CM03018

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/10/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
OK FOR FINAL
04/04/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
PROVIDE INSTALL INSTRUCTIONS FOR FAN COILS
BUILD TRAPS PER MANUFACTURES INSTRUCTIONS
YOU CANNOT RUN UPHILL AFTER TRAP
EVERYTHING ELSE IS OK
03/26/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PERMANENTLY ID FAN COILS AND CONDENSORS
2) CONDENSATE DRAINS NOT SLOPED TRAPS TOO DEEP
3) LINE SET BLOCKING REMOVAL OF BLOWER ASSEMBLY
4) BUILD TRAPS PER MANUFACTURERS INSTRUCTIONS
5) FACTORY TRAPS ARE FLATTENED AT BOTTOM OF TRAP
6) PROVIDE SUPPORT UNDER 2 LONG LINE SETS AT CONDENSORS