Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM03018
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/10/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/03/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* #1 - ROCK CANNOT BE IN FRONT OF SERVICE, NEEDS 3' MIN. CLEAR SPACE TO FLOOR - 2002 NEC 110.26 #2 - AC DISCONNECTS REQUIRED TO HAVE CLEARANCE IN FRONT ALSO, AS PER 110.26 |