Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM03003

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/23/2006 ELECTRIC - INTERMEDIATE Approved
10/16/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SECURE FIXTURES TO GRID NEC 300.11
2. J-BOXES TO BE ACCESSIBLE NEC 110
3. MAKE SURE ALL J-BOXES ARE GROUNDED AND TIGHTEN SCREW -- NEC 250.4
4. HAVE OVERFILLED J-BOXES NEC 314.16A
5. LOW VOLTAGE WIRING HANGING ACROSS CEILING -
NEC 800.6
10/11/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
INSPECTION OF AREAN AREA CEILINGS.
1. STRAP FLEX WITHIN 12" OF TERMINATIONS FOR DUCT DETECTOR WIRING.
2. MAKE SURE EMERGENCY LIGHTING COMPLIES WITH
NEC 700.12 IN ALL AREAS.
10/06/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) NOTE: DO NOT ENERGIZE ANY OPEN/UNSAFE WIRING
10/05/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
BEFORE POWER APPROVAL
1. TERMINATE ALL FEEDERS AND COMPLETE TRANSFORMER WIRING.
2. TRIM OR SAFE OFF ALL OPEN WIRING TO 8' ABOVE FLOOR
3. CALL FOR INSPECTION.
08/30/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
BOX BRACE OK OK ELECTRICAL WALL COVER
08/29/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROVIDE BACK BRACE FOR RECEPTACLE BOXES WITH MC ONLY SO THEY CAN'T ROLLBACK IN WALL -- NEC 314.23 (B)

OK ELECTRICAL COVER AFTER CORRECTION.
08/22/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK DEMISING WALL -- OK TO COVER
08/21/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER WALLS IN ARENA AREAS -- DO NOT COVER PANEL LOCATIONS.