Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM03003
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/23/2006 | ELECTRIC - INTERMEDIATE | Approved | ||
| 10/16/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SECURE FIXTURES TO GRID NEC 300.11 2. J-BOXES TO BE ACCESSIBLE NEC 110 3. MAKE SURE ALL J-BOXES ARE GROUNDED AND TIGHTEN SCREW -- NEC 250.4 4. HAVE OVERFILLED J-BOXES NEC 314.16A 5. LOW VOLTAGE WIRING HANGING ACROSS CEILING - NEC 800.6 |
|
| 10/11/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* INSPECTION OF AREAN AREA CEILINGS. 1. STRAP FLEX WITHIN 12" OF TERMINATIONS FOR DUCT DETECTOR WIRING. 2. MAKE SURE EMERGENCY LIGHTING COMPLIES WITH NEC 700.12 IN ALL AREAS. |
|
| 10/06/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) NOTE: DO NOT ENERGIZE ANY OPEN/UNSAFE WIRING |
|
| 10/05/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* BEFORE POWER APPROVAL 1. TERMINATE ALL FEEDERS AND COMPLETE TRANSFORMER WIRING. 2. TRIM OR SAFE OFF ALL OPEN WIRING TO 8' ABOVE FLOOR 3. CALL FOR INSPECTION. |
|
| 08/30/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* BOX BRACE OK OK ELECTRICAL WALL COVER |
|
| 08/29/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROVIDE BACK BRACE FOR RECEPTACLE BOXES WITH MC ONLY SO THEY CAN'T ROLLBACK IN WALL -- NEC 314.23 (B) OK ELECTRICAL COVER AFTER CORRECTION. |
|
| 08/22/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK DEMISING WALL -- OK TO COVER |
|
| 08/21/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER WALLS IN ARENA AREAS -- DO NOT COVER PANEL LOCATIONS. |