Permit: T06CM03001

Parcel: 107120690

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/29/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/27/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
ALL UNITS -- NEED 2 POLE BREAKER FOR SPLIT WIRED DISPOSAL RECEPTACLE

#11 - PANEL DIRECTORY NOT CORRECT - WATER HEATER GROUND LOOSE

#10 - PANEL DIRECTORY NOT CORRECT

GO THROUGH ALL PANEL DIRECTORIES - 2 POLE BREAKERS AT DISPOSAL RECEPTACLE - 2 NEUTRALS NOT TO BE UNDER SAME SCREWS IN PANELS

THERE MAY BE A FEE IF NOT ALL CORRECT NEXT INSPECTION
03/13/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR UNIT #12 - CHECK OTHERS FOR SAME

ON ROOF
1. HAVE DIFFERENT RTU'S THEN PLAN
2. IDENTIFY DATA PLATES - NEC 110
3. DISCONNECTS TO HAVE 36" FRONT WORKING CLEARANCE
NEC 110
4. SECURE RECEPTACLE BOX TO PEDESTAL - NEC 110

INTERIOR
1. INSTALL RANGE ANTI-TIP DEVICE - NEC 110
2. 2 NEUTRAL NOT ALLOWED UNDER SAME SCREW IN
PANEL - NEC 408
3. PROVIDE DISCONNECTING MEANS FOR WATER HEATER
NEC 422
4. NEED CONNECTOR FOR ROMEX INTO HOOD
5. PANEL DIRECTORY NOT CORRECT.
ALSO, NEEDS TO BE NEAT AND LEGIBLE -
CORRECT SPELLING DO NOT ABBREVIATE -- NEC 408.4

PARTIAL INSPECTION
CHECK REST OF UNITS FOR SAME
01/22/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*