Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/29/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/27/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ALL UNITS -- NEED 2 POLE BREAKER FOR SPLIT WIRED DISPOSAL RECEPTACLE #11 - PANEL DIRECTORY NOT CORRECT - WATER HEATER GROUND LOOSE #10 - PANEL DIRECTORY NOT CORRECT GO THROUGH ALL PANEL DIRECTORIES - 2 POLE BREAKERS AT DISPOSAL RECEPTACLE - 2 NEUTRALS NOT TO BE UNDER SAME SCREWS IN PANELS THERE MAY BE A FEE IF NOT ALL CORRECT NEXT INSPECTION |
|
| 03/13/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR UNIT #12 - CHECK OTHERS FOR SAME ON ROOF 1. HAVE DIFFERENT RTU'S THEN PLAN 2. IDENTIFY DATA PLATES - NEC 110 3. DISCONNECTS TO HAVE 36" FRONT WORKING CLEARANCE NEC 110 4. SECURE RECEPTACLE BOX TO PEDESTAL - NEC 110 INTERIOR 1. INSTALL RANGE ANTI-TIP DEVICE - NEC 110 2. 2 NEUTRAL NOT ALLOWED UNDER SAME SCREW IN PANEL - NEC 408 3. PROVIDE DISCONNECTING MEANS FOR WATER HEATER NEC 422 4. NEED CONNECTOR FOR ROMEX INTO HOOD 5. PANEL DIRECTORY NOT CORRECT. ALSO, NEEDS TO BE NEAT AND LEGIBLE - CORRECT SPELLING DO NOT ABBREVIATE -- NEC 408.4 PARTIAL INSPECTION CHECK REST OF UNITS FOR SAME |
|
| 01/22/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |