Permit: T06CM03001

Parcel: 107120690

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
01/22/2008 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
01/18/2008 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. TIGHTEN CONNECTIONS
2. INSTALL GROUND RODS
3. SELF TAP SCREWS NOT ALLOWED FOR GROUND BAR
4. IDENTIFY SERVICE DISCONNECTS
5. HOUSE PANEL - SEPARATE NEUTRALS FROM GROUNDS
BOND GROUND BAR TO ENCLOSURE