Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/20/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/11/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio PAY REFEE 201 N. STONE PRIOR TO ANY FUTURE INSPECTIONS. |
|
| 07/07/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PAY REFEE - RECALL INSP. STRAP #4 BARE WIRE TO WALL OF HOUSE AS REQUESTED ON 6/20/06 INSPECTION. |
|
| 07/03/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ADDRESS LABEL NOT ON AS REQUESTED |
|
| 06/27/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio |
|
| 06/20/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE NOTES LAST INSP. NO COMPLIANCE ALSO STRAP #4 BARE TO WALL BELOW PANEL. |
|
| 06/15/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTES: 1. EXPOSE GROUND RODS, VERIFY WATER & GAS PIPE BONDING. 2. USE APPROVED FITTING FOR LB TERMINATION INTO SERVICE ENCLOSURE - BOND BUSHING. 3. BUBBLE TYPE COVER REQUIRED FOR GFI OUTLET. 4. MAGIC MARKER NOT APPROVED FOR ADDRESS LABEL, MUST BE PERMANENT LABEL SCREWED OR RIVETED TO ENCLOSURE. 5. I.D CIRCUIT BREAKER. |