Permit: T06CM02996

Parcel: 138050530

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/20/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/11/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
PAY REFEE 201 N. STONE PRIOR TO ANY FUTURE INSPECTIONS.
07/07/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PAY REFEE - RECALL INSP.
STRAP #4 BARE WIRE TO WALL OF HOUSE AS REQUESTED ON 6/20/06 INSPECTION.
07/03/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
ADDRESS LABEL NOT ON AS REQUESTED
06/27/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
06/20/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
SEE NOTES LAST INSP. NO COMPLIANCE
ALSO STRAP #4 BARE TO WALL BELOW PANEL.
06/15/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOTES:
1. EXPOSE GROUND RODS, VERIFY WATER & GAS PIPE BONDING.
2. USE APPROVED FITTING FOR LB TERMINATION INTO SERVICE ENCLOSURE - BOND BUSHING.
3. BUBBLE TYPE COVER REQUIRED FOR GFI OUTLET.
4. MAGIC MARKER NOT APPROVED FOR ADDRESS LABEL, MUST BE PERMANENT LABEL SCREWED OR RIVETED TO ENCLOSURE.
5. I.D CIRCUIT BREAKER.