Permit: T06CM02981

Parcel: 115041730


Addresses:

1221 N EUCLID AV


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM02981

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/15/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
11/24/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE GAS AND COPPER BONDS
2) GROUND ALL METAL BOXES
3) SECURE BOX 8" FROM BOX EVERY 4' AFTER ? SECURE COPPER LINES
4) FIREBLOCK DROP CEILINGS
10/29/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MAKE UP GROUND WIRES AND GROUND METAL BOXES
2) INSTALL PLASTIC BUSHING ON NIPPLE GOING THRU WALL SO WIRES DON'T CHAFF ON METAL NIPPLE