Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/05/2006 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 06/27/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
| 06/20/2006 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SCHEDULE 60 MUST BE MINIMUM 18" COVERAGE 2) UNDERGROUND COPPER MUST BE WRAPPED ALSO, NEEDS 12" COVERAGE 3) UNDERGROUND GAS LINE OK 4) NO PLANS/INSPECTION CARD ON SITE |