Permit: T06CM02968

Parcel: 113071710

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
04/06/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
CORRECTIONS MADE OK
OK TO COVER ALL AREAS
04/02/2007 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REQUIRE 18" OF COPPER AT WATER HEATER AND AT SERVICE CONNECTION BEFORE PEX
2. PLUMBERS TAPE NOT AN APPROVED STRAP.
3. IS-5 2003 UPC ABS SHALL BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION, AND AT THE END OF BRANCHES THEN NO MORE THAN FOUR FEET BETWEEN HANGERS.
4. SUPPORT VERTICAL PIPE AT MID-STORY
5. SCREW DOWN CLOSET FLANGES WITH APPROVED FASTENERS.