Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/10/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/05/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. UPSTAIRS BATHROOM WIRING NOT STAPLED ALSO, CHECK WIRING -- THE GFI RECEPTACLE CANNOT BE WIRED TO SAME CIRCUIT AS FAN OR LIGHT AT UPSTAIRS E&W BATHROOMS. 2. BATHROOM RECEPTACLES ON SO. SIDE UNIT SAME SITUATION AS #1 SEE NEC 210.11 C-3 |
|
| 04/03/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CONNECT UFER TO SERVICE - NEC 250.50 2. NEED EXTERIOR RECEPTACLE AT REAR OF EACH UNIT NEC 210.52 ETC 3. SPACE INTERIOR RECEPTACLES PER NEC 210.52A 1, 2, 3 etc 4. PIGTAIL MULTI-WIRE NEUTRAL HOME RUNS - 300.13 B 5. NEED MORE NAIL PLATES THROUGHOUT - NEC 300.4 A1 6. HAVE HANGING WIRE (HOME RUN) IN KITCHEN? 7. PROPERLY SECURE ALL ROMEX - NEC 334.30 8. NEED SMOKE DETECTOR LOWER LEVEL 9. BATH GFI'S NOT WIRED CORRECTLY - NEC 210.11 C3 INTERIOR INSPECTION FOR SOUTH UNIT ONLY 10. CHECK KITCHEN COUNTER RECEPTACLE SPACING NEC 210.52 C |
|
| 03/30/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |