Permit: T06CM02968

Parcel: 113071710

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/10/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/05/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. UPSTAIRS BATHROOM WIRING NOT STAPLED ALSO, CHECK WIRING -- THE GFI RECEPTACLE CANNOT BE WIRED TO SAME CIRCUIT AS FAN OR LIGHT AT UPSTAIRS E&W BATHROOMS.
2. BATHROOM RECEPTACLES ON SO. SIDE UNIT SAME SITUATION AS #1 SEE NEC 210.11 C-3
04/03/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CONNECT UFER TO SERVICE - NEC 250.50
2. NEED EXTERIOR RECEPTACLE AT REAR OF EACH UNIT
NEC 210.52 ETC
3. SPACE INTERIOR RECEPTACLES PER NEC 210.52A 1, 2, 3 etc
4. PIGTAIL MULTI-WIRE NEUTRAL HOME RUNS - 300.13 B
5. NEED MORE NAIL PLATES THROUGHOUT - NEC 300.4 A1
6. HAVE HANGING WIRE (HOME RUN) IN KITCHEN?
7. PROPERLY SECURE ALL ROMEX - NEC 334.30
8. NEED SMOKE DETECTOR LOWER LEVEL
9. BATH GFI'S NOT WIRED CORRECTLY - NEC 210.11 C3

INTERIOR INSPECTION FOR SOUTH UNIT ONLY
10. CHECK KITCHEN COUNTER RECEPTACLE SPACING
NEC 210.52 C
03/30/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*