Permit: T06CM02941

Parcel: 13414001D


Addresses:

260 S PANTANO RD 02


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T06CM02941

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/28/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
11/27/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
CONTRACTOR TO PAY REFEE AS STATED AT LAST INSPECTION
WITHIN 5 WORKING DAYS OR PERMIT SHALL BE FROZEN.
1. SHALL SECURE ALL SHOWER & TUB VALVES CORRECTLY.
2. WATER TEST TO BE IN PLACE ON ALL UNITS.
3. WHILE YOU ARE DOWNTOWN PLEASE HAVE PLUMBING CONTRACTOR CHANGED ON THESE PERMIT TO SPARTAN PLUMBING.
11/21/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
PLEASE READ ALL NOTES & COMPLY WITH CORRECTIONS ON INSPECTION DATED 11/16/06 OR YOU SHALL BE REFEED
11/20/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WORKERS SHALL NOT BE SUBJECT TO SEWER GASES DURING CONSTRUCTION -- CAP OPEN PIPES.
2. POTABLE WATER SYSTEM SHALL BE PROTECTED FROM CONTAMINATION DURING CONSTRUCTION -- INSTALL VAC BREAKERS.
3. JOINTS IN WALL SHALL BE TESTED BEFORE CONCEALMENT.
4. ONLY ONE 1/2" PIPE MAY SUPPLY ONE WASHER BOX.
11/16/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
- CONTRACTOR IS SPARTAN PLUMBING
- INSTALL TEMP CAPS ON OPEN DRAIN PIPING.
- TEST SHOWER RISER AND TUB SPOUT OUTLETS.
- INSTALL HB VAC BREAKERS OR NEW WATER HEATERS REQUIRE PERMITS AND DRAIN PANS ON SECOND FLOOR.
- OK TO CONNECT DRAIN AND COVER FLOORS.
- RFI WATER PIPE SIZE FOR BACK TO BACK WASHER BOX.
- ONE 1/2" PIPE SERVES TWO WASHER BOXES, THIS MAY NOT BE ADEQUATE. PLAN DOES NOT SHOW SIZING FOR BOTH.