Permit: T06CM02940

Parcel: 13414001D


Addresses:

260 S PANTANO RD 01

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
06/20/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
#104, 105, 106, 203, 204, 205, 206, 112, 211, 212, 110, 210 OK
05/10/2007 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
UNITS # 101, #102, #103. #107, #108, #109, #111, #201, #202, #207, #208, #209 ALL OK
05/08/2007 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
UNIT 209 -- OFFSET ON TRAP ARM NOT ALLOWED, PROVIDE CORRECT LENGTH TAILPIECE. DOUBLE FLEX ON WH SUPPLY. EXTERIOR CLEANOUTS SHALL TERMINATE AT GRADE W/PROPER FITTING. MAKE CLEANOUTS WATER AND GAS TIGHT WITH THREAD SEALANT. TEMP PLUG OPEN DRAINS IN OTHER UNITS. REMOVE DIRT AT T&P TERMINATIONS.
QUICK CLOSING VALVES REQUIRE HAMMER ARRESTORS PER 2003 UPC SEC 609.10
ROOF OK
INSPECTED UNITS 101-103, 107-109, 201, 202, 207-209
04/26/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
COMPLETE ALL PLUMBING WORK & ITEMS LISTED ABOVE FROM PAST INSPECTION. FAILURE TO COMPLY SHALL RESULT IN REFEE. ALL WATER HEATERS ARE TO BE CORRECTLY PIPED.
04/24/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELLED
03/15/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
PROVIDE BUILDING # SIGNAGE
1. DISHWASHER DRAINAGE HOSE TO HAVE HIGH LOOP & CLAMP
TO SECURE.
2. CONDENSATE DRAINAGE TO LAVS TO BE FULL SIZE 3/4" TO TERMINATION INTO 3/6" BRANCH TAIL PIECE
3. VACUUM BREAKERS AT ALL HOSE BIBS
4. PROVIDE FACTORY TAPPED CLEANOUT PLUGS & MACHINE SCREWS & COVERS T0 PREVENT VERMIN ENTRY. WHERE CLEANOUTS ARE INSTALLED.