Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/20/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* #104, 105, 106, 203, 204, 205, 206, 112, 211, 212, 110, 210 OK |
|
| 05/10/2007 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* UNITS # 101, #102, #103. #107, #108, #109, #111, #201, #202, #207, #208, #209 ALL OK |
|
| 05/08/2007 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* UNIT 209 -- OFFSET ON TRAP ARM NOT ALLOWED, PROVIDE CORRECT LENGTH TAILPIECE. DOUBLE FLEX ON WH SUPPLY. EXTERIOR CLEANOUTS SHALL TERMINATE AT GRADE W/PROPER FITTING. MAKE CLEANOUTS WATER AND GAS TIGHT WITH THREAD SEALANT. TEMP PLUG OPEN DRAINS IN OTHER UNITS. REMOVE DIRT AT T&P TERMINATIONS. QUICK CLOSING VALVES REQUIRE HAMMER ARRESTORS PER 2003 UPC SEC 609.10 ROOF OK INSPECTED UNITS 101-103, 107-109, 201, 202, 207-209 |
|
| 04/26/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* COMPLETE ALL PLUMBING WORK & ITEMS LISTED ABOVE FROM PAST INSPECTION. FAILURE TO COMPLY SHALL RESULT IN REFEE. ALL WATER HEATERS ARE TO BE CORRECTLY PIPED. |
|
| 04/24/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* CONTRACTOR CANCELLED |
|
| 03/15/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* PROVIDE BUILDING # SIGNAGE 1. DISHWASHER DRAINAGE HOSE TO HAVE HIGH LOOP & CLAMP TO SECURE. 2. CONDENSATE DRAINAGE TO LAVS TO BE FULL SIZE 3/4" TO TERMINATION INTO 3/6" BRANCH TAIL PIECE 3. VACUUM BREAKERS AT ALL HOSE BIBS 4. PROVIDE FACTORY TAPPED CLEANOUT PLUGS & MACHINE SCREWS & COVERS T0 PREVENT VERMIN ENTRY. WHERE CLEANOUTS ARE INSTALLED. |