Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM02940
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/22/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/20/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. 211 NOT READY 2. 110 NEED ANTI-TIP ON RANGE & GFI RECEPT KITCHEN COUNTER. 3. 210 NEEDS GFI RECEPT KITCHEN COUNTER 4. 106 DINING ROOM RECEPT. MISSING GROUND 5. OK FINALS 104, 105, 112, 203, 204, 205, 206, 212 |
|
05/10/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK BOX EXTENSIONS AT OUTDOOR RECEPTACLES |
|
04/26/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
04/24/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK UNITS 101, 102, 103, 107, 108, 109, 111, 201, 202, 207, 208, 209 2. ELECTRIC FINAL OK ON ABOVE UNITS |
|
03/15/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL BOX EXTENSION ON RECEPT UNDER KITCHEN SINK ALL UNITS 2. APARTMENT 107 HAS POWER PROBLEM MASTER BEDROOM 3. UNIT 209 REVERSE POLARITY AT BATHROOM RECEPT 4. CHECK AROUND MAKE UP AT ALL LIGHT FIXTURES ALL UNITS. 5. INSTALL IN USE COVERS (BUBBLE COVERS) ON OUTSIDE RECEPT EXPOSED TO WEATHER. 6. INSPECTED UNITS 101, 102, 103, 107, 108, 109, 111, 201, 201, 207, 208, 209 |