Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM02935
Inspection Description - FRAMING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/13/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 07/10/2006 | FRAMING | Partial Approval | IVRS - Inspection :* 1) 03050 ITEM NOT REQUIRED-ALL ELECTRIC 2) FURNACE IN ATTIC, PLAN SHOWS IN GARAGE 3) RELOCATE A/C POWER 4) NEED ELECTRIC FURNACE HOME RUN SIZE, #8 INSTALLED PLAN CALLS FOR 60 AMP CIRCUIT 5) VERIFIED H.D. BEHIND SHOWER, WRONG NAILS IN H.D. BEHIND SHOWER, WRONG NAILS IN H.D.'S 6) GARAGE SHEAR 5/8" DIAMETER A.B. AT 24" ON CENTER 7) NEED DWV, POTABLE H20 TEST |