Permit: T06CM02934

Parcel: 141314170

Inspection Status: Approved

Inspection History: STUCCO MESH

Permit Number - T06CM02934

Inspection Description - STUCCO MESH

Inspection Status - Approved

Date Description Inspector Results Comments
07/26/2006 STUCCO MESH Approved IVRS - Inspection :*
07/13/2006 STUCCO MESH Partial Approval IVRS - Inspection :*
1) WIRE SIZES FOR A/C AND FURNACE AT FINAL-WILL INSPECT PER U.L. LABEL EQUIPMENT MINIMUM CLR. AMP AND BREAKER SIZE. CHECK WIRE SIZES-THEY ARE NOT PER PLAN
2) TAPE DRYER DUCT
3) OK TO INSULATE
07/10/2006 STUCCO MESH Partial Approval IVRS - Inspection :*
1) NEED H20 TEST, DWV/H20 POTABLE, PROTECT PEX SEE MARK ON FLOOR
2) ITEM 03050 NOT REQUIRED-ALL ELECTRIC
3) H.D.'S REQUIRE SPECIFIC BOLTS, NAIL SIZE-SEE PLAN
4) CUT NAIL PLATE TO FLOOR MARKED
5) BLK AT CONDENSATE GARAGE
6) BLK SIDES OF SHOWER, MASTER SCREW SURROUND HALL BATH
7) NOTCH T/PLATE NON-BEARING TRUSSES, NEAR ENTRY
8) RECEPT TO BE 1' FROM TOP OF BAR TOP OR REMOVE
9) NEED SHEAR TRANSFER FOR AT #2 SHEAR 3 PT BEARING
10) ATTACH TOP PLATE PER 10/DT1 SHEAR
11) MOVE OR REMOVE RECEPT AT SHORT KITCHEN WALL
12) PLAN NOT NOTED FOR ELECTRIC FURNACE HOME RUN WIRE SIZE
13) A/C CIRCUIT ON PLAN TO BE #6-60 AMP